ALARMS-MAXIMUM-PER-DEFINITION

(server version 4.06 or later)

 

(Default = 100)

ALARMS-MAXIMUM-PER-DEFINITION  <value16> 

 

Specifies the maximum number of Alarms that a single definition is allowed to generate.

 

This value is primarily a protection mechanism to prevent a single definition from generating an excessive number of Alarms. Once the limit is reached, a special 'really red' or purple alarm is displayed and further alarms from the definition are disabled. Update the Alarm definition to 'reset' or clear the 'really red' alarm.

 

 

Example:

 

                               == Alarms maximum to 175

ALARMS-MAXIMUM-PER-DEFINITION 175